YASKAWA U1000 Quick Start Manual page 48

Industrial matrix drive
Hide thumbs Also See for U1000:
Table of Contents

Advertisement

i.4 Electrical Installation
Mode
Sinking Mode
Sourcing Mode
u
Using the Pulse Train Output
The pulse train output terminal MP can supply power or be used with an external power supply.
NOTICE: Connect peripheral devices in accordance with the specifications. Failure to comply may cause unexpected drive operation, and
can damage the drive or connected circuits.
n
Using Power from the Pulse Output Terminal (Source Mode)
The high voltage level of the pulse output terminal depends on the load impedance.
Load Impedance R
Note:
The load resistance needed in order to get a certain high level voltage V
n
Using External Power Supply (Sink Mode)
The high voltage level of the pulse output signal depends on the external voltage applied. The voltage must be between 12
and 15 Vdc. The load resistance must be adjusted so that the current is lower than 16 mA.
External Power Supply (V)
12 to 15 Vdc ±10%
48
Table i.18 Safe Disable Input Sink/Source/External Power Supply Selection
Drive Internal Power Supply
Jumper S3
HC
H1
H2
Jumper S3
HC
H1
H2
(kΩ)
L
1.5 kΩ
4 kΩ
10 kΩ
MP
AC
Figure i.32 Pulse Output Connection Using Internal Voltage Supply
24 Vdc
24 Vdc
Output Voltage V
can be calculated by: R
MP
Load Impedance
V
R
MP
L
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide
External 24 Vdc Power Supply
Jumper S3
24 Vdc
HC
External
24 Vdc ±10%
H1
H2
Jumper S3
24 Vdc
HC
24 Vdc ±10%
H1
H2
(V) (insulated)
MP
5 V
8 V
10 V
• 2 / (12 – V
= V
L
MP
Load Impedance (kΩ)
1.0 kΩ or higher
)
MP

Hide quick links: