u
Terminal A2 Input Signal Selection
Terminal A2 can be used to input either a voltage or a current signal. Select the signal type using switch S1 as explained in
Table
i.19. Set parameter H3-09 accordingly as shown in
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Setting
V (left position)
I (right position)
No.
Parameter Name
H3-09
Terminal A2 Signal Level Selection
u
Terminal A3 Analog/PTC Input Selection
Terminal A3 can be configured either as multi-function analog input or as PTC input for motor thermal overload protection.
Use switch S4 to select the input function as described in
Setting
AI (lower position) (default)
PTC (upper position)
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in
Table
i.22. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Terminal
Terminal AM
Terminal FM
YASKAWA ELECTRIC TOEP C710636 04D U1000 Industrial MATRIX Drive Quick Start Guide
External Power Supply
MP
AC
Figure i.33 Pulse Output Connection Using External Voltage Supply
Table i.19 DIP Switch S1 Settings
Current input (4 to 20 mA or 0 to 20 mA): default setting
Table i.20 Parameter H3-09 Details
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
3: 0 to 20 mA
Table i.21 DIP Switch S4 Settings
Analog input for the function selected in parameter H3-06
PTC input. Parameter H3-06 must be set to E (PTC input)
Table i.22 Jumper S5 Settings
Voltage Output
V
I
FM
AM
V
I
FM
AM
Load Impedance
Sink Current
Table
i.20.
Description
Voltage input (-10 to +10 V or 0 to 10 V)
Description
Table
i.21.
Description
i.4 Electrical Installation
Setting Range
Default Setting
0 to 3
Current Output
V
I
FM
AM
V
I
FM
AM
2
49