Immunity Requirements - GE AF-650 GP Design And Installation Manual

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Installation Consideration
7.1.3 EMC Test Results (Emission)
The following test results were obtained using a system
with an adjustable frequency drive (with options, if
RFI filter type
Standard
Class A1/B RFI Filter installed
1–60 hp [0.75–45 kW] 200–240
V
1–125 hp [0.75–90 kW] 380–
480 V
Class A2 RFI Filter installed
1–5 hp [0.75–3.7 kW] 200–240
V
7.5–50 hp [5.5–37 kW] 200–240
V
1–10 hp [0.75–7.5 kW] 380–480
V
15–100 hp [11–75 kW] 380–
480 V
125–1,075 hp [90–800 kW]
380–480 V
125–1,600 hp [90–1,200 kW]
525–690 V
No RFI Filter installed
1–100 hp [0.75–75 kW] 525–
600 V
Table 7.3 EMC Test Results (Emission)

7.2 Immunity Requirements

The immunity requirements for adjustable frequency drives
depend on the environment where they are installed. The
requirements for the industrial environment are higher
than the requirements for the home and office
environment. All GE adjustable frequency drives comply
with the requirements for the industrial environment and
consequently comply also with the lower requirements for
home and office environment with a large safety margin.
In order to document immunity against electrical
interference from electrical phenomena, the following
immunity tests have been made on a system consisting of
an adjustable frequency drive (with options if relevant), a
shielded control cable and a control box with potenti-
ometer, motor cable and motor.
TM
AF-650 GP
Design and Installation Guide
Conducted emission.
Maximum shielded cable length.
Industrial environment
EN 55011
EN 55011
Class A2
Class A1
500 ft [150 m]
500 ft [150 m]
500 ft [150 m]
500 ft [150 m]
16.4 ft [5 m]
No
82 ft [25 m]
No
16.4 ft [5 m]
No
82 ft [25 m]
No
500 ft [150 m]
No
500 ft [150 m]
No
-
-
DET-767A
relevant), a shielded control cable, a control box with
potentiometer, as well as a motor and motor-shielded
cable.
Housing, trades
Industrial
and light
environment
industries
EN 55011
EN 55011
Class B
Class A1
164 ft [50 m]
Yes
164 ft [50 m]
Yes
No
No
No
No
No
No
No
No
No
No
No
No
-
-
The tests were performed in accordance with the following
basic standards:
EN 61000-4-2 (IEC 61000-4-2): Electrostatic
discharges (ESD): Simulation of electrostatic
discharges from human beings.
EN 61000-4-3 (IEC 61000-4-3): Incoming electro-
magnetic field radiation, amplitude modulated
simulation of the effects of radar and radio
communication equipment as well as mobile
communications equipment.
EN 61000-4-4 (IEC 61000-4-4): Electrical
interference: Simulation of interference brought
about by switching a contactor, relay or similar
devices.
Radiated emission
Housing, trades and light
industries
EN 55011
Class B
No
No
No
No
No
No
No
No
-
7-3
7
7

Advertisement

Table of Contents
loading

Table of Contents