Attention!
In case the flameproof joint has been damaged mechanically, the housing
must not be used anymore!
Attention!
Do not lock-in any foreign objects inside the housing
-
Only the original screws as part of the delivery scope may be used. They have to
be clean and intact. Demounted screw locks (washer spring DIN 127 A) have to
be re-assembled
-
The Gylon sealing must be intact and has to be reassembled according to the ho-
le-pattern of the flange. There is no restriction regarding the installation direction of
the sealing
-
If, when closing the housing, it is noted that the surface of the flameproof joint is
dirty or not lubricated sufficiently, please clean it with a clean cloth and suitable
cleaning deter-gent. Afterwards, re-lubricate it with a suitable lubrication agent
-
The screw connection of the flange and housing have to be tightened in crosswise se-
quence with a torque of 3 Nm Please avoid extensive tightening – this might lead to a
torn screw resulting into damaging the housing's pressure resistance and / or ignition
protection level
Doc.-ID: 140721-PT08BAU-SS-Ex Installation Manual rev.03 (1st Supplement), page 20 of 52