Dismantling the SVI II AP from Rotary Valves
Before carrying out any work on the device, power off the instrument or ensure that the device's
location conditions for potentially explosive atmosphere permit the safe opening of the cover.
To remove the SVI II AP Controller from a rotary valve perform Steps 1 - 9 on page 22 in reverse.

Mounting the SVI II AP on Reciprocating Valves

The process of mounting the SVI II AP on a reciprocating valve consists of mounting the unit on
the actuator that is attached to the valve. This section describes the procedure for mounting the
SVI II AP on Reciprocating Valves (using Masoneilan's 87⁄88 Multi-Spring actuators as an exam-
ple).
Mounting the SVI II AP on a Reciprocating Actuator
Tools required:
1. Ensure that the lever is pinned to the magnet assembly and held securely by an
M5 flat head screw to ensure that the magnet axis is vertical when the lever is in
the valve closed position. Tighten the lever screw securely. Refer to Figure 10.
© 2015 General Electric Company. All rights reserved
7⁄16" Combination Wrench (2 required)
3⁄8" Combination Wrench
1⁄2" Combination Wrench
Phillips Head Screw Driver
5 mm Hex Key Wrench
Figure 10 Magnet Holder for Reciprocating Valves
.
Masoneilan SVI II AP Digital Positioner Quick Start Guide =| 25
M5 Flat
head screw
Pin