Table 10: Input Signal, Power, and Display Specifications
Power Supply
Compliance Voltage Rating
Minimum Current Signal to Start Up
Minimum Input Span for Split Range Operation
Upper Range Value for Split Range Operation
Lower Range Value for Split Range Operation
Wire Size
Strip Length
Digital Communication
Local Display
Push Buttons
Housing and Cover
Weight
Relay and Manifold
I/P Motor
Mounting Bracket
Magnet Holder
Pole Ring
Levers
© 2015 General Electric Company. All rights reserved
Table 11: Construction Material Specifications
Aluminum ASTM B85 SG100A standard
Stainless Steel optional
Standard Flow Model:
- Aluminum - 7.4 lbs./ 3.3 kg
- Stainless Steel - 16 lbs/ 7.3 kg
High Flow Model:
- With Display: 9.4 lbs./ 4.2 kg
- Without Display: 8.9 lbs./ 4.0 kg
Standard Flow Model:
Single Acting - PPS, 300 Series Stainless Steel, nitrile diaphragms
Double Acting - 300 Series Stainless Steel, Ryton
Aluminum 6061 T6, Ryton
High Flow Model:
300 Series Stainless Steel, Ryton
430 stainless steel, PPS, 300 series stainless steel
300 series stainless steel
Corrosion Protected Anodized Aluminum 6061 T6
416 stainless steel
300 Series stainless steel
Loop powered from 4-20 mA control signal
9.0 V at 20 mA, 11.0 V at 4.0 mA
3.2 mA
5 mA
8 mA to 20 mA
4 mA to 14 mA
14/28 AWG
0.22 in / 6 mm
®
HART
Communication protocol revision 5 or 6
LCD, Explosion proof with two lines of nine alpha numeric
characters
External, Three Explosion Proof / Flameproof push buttons
Aluminum 6061 T6, Ryton
.