Check-out with a HART
If the SVI II AP is not equipped with optional push buttons and local display the checkout and con-
figuration is performed using the standard HART
C
onnect the HART
product manual for the HART
Input Signal
Be sure that the configuration lock jumper is in the unlock position. When the jumper is in the lock
position (shorting the two-pin header) the handheld is not permitted to make any changes. How-
ever, parameters are readable. If fault messages appear, they must be handled before proceed-
ing with HART
communications. Before communications proceeds all error messages must be
®
cleared. For example, the following message is displayed if the instrument has been serviced and
the air is not connected.
NOTE
© 2015 General Electric Company. All rights reserved
Handheld Communicator
®
handheld communicator to the SVI II AP as shown in Figure 27. Refer to the
®
communicator in use.
®
Figure 27 SVI II AP HART
Process applied to the non-primary variable is outside the
operating limits of the field device
For HART
Additional Status does not indicate any maintenance need.
communications interface.
®
Configuration
Lock Jumper
®
Communicator Connections
6 units, the Maintenance Required response under
®
.
Masoneilan SVI II AP Digital Positioner Quick Start Guide =| 53