HART
Physical Device Type
DD Registered with HART
cation Foundation
Integration with HART
Diagnostics
Table 13: Pneumatics Single Acting Standard Flow
Air Supply
Action
Supply Pressure
Air Delivery - Single Acting Relay
Air Capacity
(flow coefficient)
Air Consumption
Air Supply Failure
Loss of Input Signal
Output Pressure
62 | =GE Oil & Gas
Table 12: System Connectivity
Valve positioner; HART
®
Communi-
Yes
®
Host software
ValVue AMS SNAP-ON application available, Plug-In Application For Yok-
ogawa
FDT Host
Standard:
Alarms, cycle counter, travel accumulator, time open, time close, time near
close, Step Test, Positioner Test
Advanced:
Includes Standard Diagnostics and the following: Low Air Supply alarm,
Valve Signature (Friction, spring range, seat profile)
®
device type 7, Device type 202, 0, 00CA)
®
PRM, ValVue For Honeywell
Dry, oil-free, 5 micron filtered air (per ISA S7.3)
Direct Acting
20-100 psi max. (1.4 to 6.9 bar)
Regulate 5 to 10 psi above actuator spring range. Do not
exceed actuator rating.
10.0 scf/min. (283 l/min) at 30 psi (2.1 bar) supply
16.6 scf/min. (470 l/min) at 60 psi (4.2 bar) supply
23.3 scf/min. (660 l/min) at 90 psi (6.3 bar) supply
Loading
CV = 0.57
Venting
CV = 0.53
0.2 scf/min. (5.7 sl/min) at 30 psi (2.1 bar) supply
0.26 scf/min. (7.4 sl/min) at 45 psi (3.1 bar) supply
Single Acting Relay
On supply failure the actuator output fails to atmosphere.
Some overshoot may occur when air pressure returns after a
period without air supply pressure. Always set control set
point to 0%, and put the process control system in manual,
for smooth recovery from air supply failure.
Actuator Output fails to atmosphere
0-150 psi (10.3 bar) max
© 2015 General Electric Company. All rights reserved
®