E.4 Calibration - Emerson DL8000 Instruction Manual

Preset controller
Hide thumbs Also See for DL8000:
Table of Contents

Advertisement

E.4
Calibration
Warning
Caution
Revised February-2016
Press this key to...
CLEAR
BKSP
ENTER
Right Arrow
Left Arrow
Up Arrow
Down Arrow
When performing calibrations, DO NOT remove a module after you start
the calibration process. The system cannot automatically detect a
module being removed and this may affect the results of your
calibration.
The keypad display program enables you to calibrate:
 Additive Meter
 Analog Input
 RTD
 Product Meter
During calibration, the DL8000 times-out and reconnects if left idle for
an extended period. In this case, you lose all calibration values and
must reconnect to the DL8000 and restart the calibration. No error or
warning message occurs.
Each calibration process has its own menu. Select Calibration in
program mode. The Calibration menu displays:
 14/03/12 12:26:02
For traversing use
UP
| DOWN
LEFT | RIGHT
ENTER to continue
EXIT to Go Back
EXIT to quit
Select an option to display a calibration menu.
: If you select any calibration option, the DL8000 first checks the
Note
status of the W&M switch. If the switch is locked, the DL8000
prevents the calibration and displays a message:
DL8000 Keypad Display
DL8000 Preset Instruction Manual
Do this...
Clr param data (clear the data entry for the
parameter)
Clr last char entry
This key clears only the last character and
not the entire value (use CLEAR for that).
To update value
Jump to next page (provided the number of
pages is greater than 1)
Jump to prev page (provided the number of
pages is greater than 1)
Move to Next Line
Move to Prev Line
Additive Calib
Analog Calib
RTD Calib
PRODUCT Calib
(Pg:1/1)