Calibrating Additive Meters - Emerson DL8000 Instruction Manual

Preset controller
Hide thumbs Also See for DL8000:
Table of Contents

Advertisement

DL8000 Preset Instruction Manual
E.4.1 Calibrating Additive Meters
E-50
 14/03/12 12:26:02
WM Switch is Closed
Pls open the Switch
And try again
You must open the W&M switch in order to perform calibrations.
Select Additive Calib to start the additive calibration process.
 14/03/12 12:26:02
For traversing use
UP
| DOWN
LEFT | RIGHT
ENTER to continue
EXIT to Go Back
EXIT to quit
If no additives are currently configured, the preset displays the
following screen:
 14/03/12 12:26:02
Adtv not configured
EXIT to quit
Press EXIT to quit; no calibration is possible.
In addition to the number of configured additives, the program can
display the following error messages:
Error Message
Adtv Prog. Not Available or
Running
Invalid Injection Method
K.F not configured
M.F not configured
DL8000 Keypad Display
Additive Calib
Analog Calib
RTD Calib
PRODUCT Calib
(Pg:1/1)
Description
The additive program (#4) is not loaded
or running.
The value of the injection method
[67,X,1] is not Control (value 3)
The Volume oper pulse/K –factor
parameter [67,x,2] is set to 0
The Additive Meter Factor parameter
[67,x,28] is set to 0
Revised February-2016