3 — PROGRAMMABLE PARAMETERS:
PARAMETER
Main Enable
Main_Enable
OptionBits1 [Bit 0]
Pull In Voltage
Main_Pull_In_Voltage
Holding Voltage
Main_Holding_Voltage
Battery Voltage Compensated
Main_Driver_Battery_Voltage_
Compensated
Main_Driver_Battery_Voltage_
Compensated_Bit0 [Bit 0]
Interlock Type
Interlock_Type
44
Main Contactor Parameters

MAIN CONTACTOR MENU

ALLOWABLE
RANGE
On/Off
When programmed On, the controller's native software controls the main
On/Off
contactor when the interlock is enabled or when Pump_Throttle >0.
When programmed Off, the contactor is controlled by VCL. Note: With
Main Enable programmed Off, the controller will not be able to open the
main contactor in serious fault conditions and the system will therefore not
meet EEC safety requirements.
0–100 %
The main contactor pull-in voltage parameter allows a high initial voltage
0–32767
when the main contactor driver first turns on, to ensure contactor closure.
After 1 second, this peak voltage drops to the contactor holding voltage.
To protect the driver hardware from overcurrent, the software puts a
limitation on driver output PWM. A PWM output of 1–59% is not allowed
and the software will "round up" the PWM to 60%. Setting this parameter
to a value <60% will therefore result in an output PWM of at least 60%.
Note: The Battery Voltage Compensated parameter (below) controls
whether the pull-in and holding voltages are battery voltage compensated.
0–100 %
The main contactor holding voltage parameter allows a reduced average
0–32767
voltage to be applied to the contactor coil once it has closed. This param-
eter must be set high enough to hold the contactor closed under all shock
and vibration conditions the vehicle will be subjected to.
To protect the driver hardware from overcurrent, the software puts a
limitation on driver output PWM. A PWM output of 1–59% is not allowed
and the software will "round up" the PWM to 60%. Setting this parameter
to a value <60% will therefore result in an output PWM of at least 60%.
Note: The Battery Voltage Compensated parameter (below) controls
whether the pull-in and holding voltages are battery voltage compensated.
On/Off
This parameter determines whether the main pull-in and holding voltages
On/Off
are battery voltage compensated. When set On, the pull-in and holding
voltages are set relative to the set Nominal Voltage (see Battery menu,
page 55). In other words, the output voltage is adjusted to compensate for
swings in battery voltage, so the percentage is relative to the set Nominal
Voltage—not to the actual voltage.
For example, suppose Nominal Voltage is set to 48V and Holding
Voltage is set to 75% (36V) to the output driver. Now suppose the bus volt-
age dips to 40V. If Battery Voltage Compensated = On, the output will still
be 36V (Nominal Voltage × Holding Voltage) to the coil. If Battery Voltage
Compensated = Off, the output will be 30V (Actual Voltage × Holding Volt-
age) to the coil.
0–2
Three interlock options are available:
0–2
0 = interlock turns on with switch 3.
1 = interlock controlled by VCL functions.
2 = interlock turns on with KSI.
DESCRIPTION
Curtis 1298 Manual,
11
OS