CLI Commands: Base
mirror
Configure the IO-Module mirroring for one or all digital outputs.
This command determines the input mirrored to the currently selected
output.
To disable mirroring, the following commands are equivalent:
digital-output mirror 1/2 disable
digital-output mirror 1/2 from 0.0.0.0 1/1
<all>: Configure the IO-Module mirroring for all digital outputs.
<slot/output>: Configure the IO-Module mirroring for a single
digital output. The <slot> value determines the IO-module slot
number on the device with the selected IP address.
disable: Disable the IO-Module mirroring for a single digital
output.
from: Enable the IO-Module mirroring for a single digital output from
<IP-address> <slot/input>
<IPaddress>: The IP address value detemines the IP address
used for reading the input value. Use IP address 127.0.0.1 or the sys-
tem IP address to mirror inputs from a local IO module. When IP
address is 0.0.0.0 no input is mirrored to the output (the output value
is set to 'low'). Default: 0.0.0.0.
<slot/input>: The <input> value determines the input number on
this device. Default: 1/1.