8 Electrical configuration and putting into operation

WARNING
When in use parts of electrical devices inevitably are subject to dangerous voltage currents.
Non-observance of the operating instructions can therefore lead to severe bodily harm or damage
to property.
It is imperative that the warning notices should be observed.
During the putting into operation of the controls (especially at the automatic parameter
determination) the door movement cannot always be influenced from outside. The light barrier is
not active during the teach-in drive.
It should therefore be ensured by an authorised person, who stands at the door, that no other
person comes near the elevator door during the putting into operation. The acceptable forces and
energies on the complete system (elevator) should be tested by service staff after the putting into
operation of the elevator door.
NOTICE
At the parameter teach-in drive the motor temperature may not lie below 0° C, otherwise the value
of the door weight is determined incorrectly and the closing speed and nudge speed can be in a
range not allowed.
1.
Push door in "CLOSE" position.
.
Open housing lid.
3.
Plug in motor plug X7.
NOTICE
So that no uncontrolled trips are started during the putting into operation, the plug X6 for the
control inlets is not plugged in.
4.
Connect mains current transformer with mains (30V AC). The onsite circuit breaker may
amount to a maximum of 10A.
5.
Press the red "DOOR PARAM" button (S5000) and keep pushed in.
6.
Connect outlet of mains current transformer to X3.
7.
Press red "DOOR PARAM" button (S5000) so long
until the 7-segment display (H5000) displays "_".
8.
After a short pressing of the "OPEN" (S5001) or "CLOSE" button (S5002) the teach-in trip is
started. The 7-segment display (H5000) displays "H".
The teach-in trip includes an approximately 10 cm wide opening and closing at creep speed
once or twice.
Subsequently an opening and closing once over 5 cm at creep speed follows for the ..
determination of the friction of the door system.
Thereafter the door opens and closes at reduced speed (complete trip). Herewith a short
additional acceleration incline is passed
through at the opening after an approximately 10 cm trip to determine the door weight.
The door parameter and the detected door width are stored in the "CLOSE" position.
The 7-segment display (H5000) displays "u".
9.
The door can now be opened with the "OPEN" button (S5001).
The 7-segment display (H5000) displays "o" during the opening.
10. Switch off control by pulling of the mains plug or of plug X3.
Operating Manual - Elevator Door Operation AT18