Simplified Operation Of The Vf-S15 - Toshiba VF-S15 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

3.2

Simplified Operation of the VF-S15

Operation command and Operation frequency command are necessary to operate the inverter.
Operation method and operation frequency setting can be selected from the following.
At default setting, the inverter runs and stops with RUN/STOP key on the panel keypad, and frequency can be set
with the setting dial.
Run / Stop
3
Setting the frequency
Use the basic parameters cmod (command mode selection)
andfmod (frequency setting mode selection) for selection.
[Parameter setting]
Title
cmod
fmod
☆ fmod=0 (setting dial 1) is the mode that after the frequency is set by the setting dial, the frequency is saved
even if the power is turned off. The usage of this setting dial is similar to that of potentiometer.
☆ Refer to section 5.6 for details about fmod=4 to 7,11, and 14.
: (1) Run and stop using the panel keypad
(2) Run and stop using external signals
: (1) Setting using setting dial
(2) Setting using external signals
(0-10Vdc, 4-20mAdc, -10-+10Vdc)
Function
Command mode selection
Frequency setting mode
selection 1
Adjustment range
0: Terminal block
1: Panel keypad (including extension panel)
2: RS485 communication
3: CANopen communication
4: Communication option
0: Setting dial 1(save even if power is off)
1: Terminal VIA
2: Terminal VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal VIC
9, 10: -
11: Pulse train input
12, 13: -
14: sro
C-4
E6581611
Default setting
1
0