60 Hz default setting (typ=2)
Setting typ to 2 sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
Maximum frequency (fh)
Base frequency 1 (vl)
VIA input point 2 frequency (f204) :60Hz
VIC input point 2 frequency (f219) :60Hz
Process upper limit (f367)
Motor rated speed (f417)
Default setting 1 (typ = 3)
Setting typ to 3 will return parameters to the default settings (exclusive of some parameters).
When 3 is set, init is displayed for a short time after the settings are configured, and then
disappears. Then the inverter is in standard motor mode. In this case, the trip history data is cleared.
Be aware that the following parameters do not return to the default settings even if typ=3 is set for
maintainability. (To initialize all parameters, set typ=13)
・aul:Overload characteristic selection
・fmsl:Meter selection
・fm:Meter adjustment gain
・set:Checking the region setting
・f107:Analog input terminal selection
・f109:Analog/logic input selection (VIA/VIB)
* Refer to "Communication manual" about parameter cxxx.
Trip record clear (typ = 4)
Setting typ to 4 initializes the past eight sets of recorded error history data.
The parameter does not change.
Cumulative operation time clear (typ = 5)
Setting typ to 5 resets the cumulative operation time to the initial value (zero).
Initialization of type information (typ = 6)
Setting typ to 6 clears the trips when an etyp format error occurs. But if the displayed, contact
your Toshiba distributor.
Upper limit frequency (ul)
:60Hz
Base frequency 2 (f170)
:60Hz
VIB input point 2 frequency (f213):60Hz
Automatic light-load high-speed operation
:60Hz
frequency (f330)
-1
Communication command point 2 frequency
:1710 min
(f814)
・f470~f475:VIA/VIB/VIC input bias / gain
・f669:Logic output/pulse train output selection
・f681:Analog output signal selection
・f691:Inclination characteristic of analog output
・f692:Analog output bias
・f880:Free notes
D-11
E6581611
:60Hz
:60Hz
:60Hz
:60Hz
4