Terminal
Input /
symbol
output
Multifunction programmable analog
output. Default setting: output frequency.
The function can be changed to ammeter,
FM
Output
0-10Vdc voltage or 0-20mAdc (4-20mA)
current output by parameter 
setting.
Resolution Max. 1/1000.
Output
24Vdc power output
P24
This terminal can be used as a common
Input
terminal when an external power supply
is used by changing SW1 to PLC side.
+24
Output
24Vdc power output
DC power input terminal for operating the
control circuit. Connect a control power
+SU
Input
backup device (option or 24Vdc power
supply) between +SU and CC.
Function
1mAdc full-scale
ammeter or
QS60T(option)
0-20mA (4-20mA)
DC ammeter
Permissible load
resistance:
600Ω or less
0-10V DC volt
meter
Permissible load
resistance:
1kΩ or more
24Vdc-100mA
Note 2)
24Vdc-100mA
Note 2)
Voltage: 24Vdc±
10%
Current: 1A or
more
B-9
Electrical
Inverter internal circuits
specifications
+24V
FM
P24
SW1
-
+24
1
+SU
E6581611
121
+
+24V
Voltage
Current
+
68
2
EXT
+24V
Current
limiter
+24V