Advertisement

5) Overload characteristic selection aul
Overload characteristic of inverter can be selected to 150%-60s or 120%-60s.
[Parameters settings]
Title
aul
Regarding to characteristic for aul=1 setting, refer to section 3.5.3).
Note 1) In case of aul=2 setting, be sure to install the input AC reactor (ACL) between power supply and inverter.
aul=2 (Variable torque characteristic), f631=0 (120%-60s)
5
Inverter overload
time [s]
Function
Overload characteristic selection
60
0
105%
Inverter overload protection characteristic
Adjustment range
0: -
1: Constant torque
characteristic(150%-60s)
2: Variable torque
characteristic(120%-60s)
Current
[%]
106
110
115
120
140
165
Monitored output current [%]
120%
100%: Inverter rated output current
E-14
Default setting
0
Inverter overload time [s]
(Outline data)
900
180
90
60
2
0.5
E6581611