4.3.2
typ : Default setting
 Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title
4
typ
This function will be displayed as 0 during reading on the right. This previous setting is displayed.
Example: 3
typ cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (typ=1)
Setting typ to 1 sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
 Maximum frequency (fh)
 Base frequency 1 (vl)
 VIA input point 2 frequency (f204) :50Hz
 VIC input point 2 frequency (f219) :50Hz
 Process upper limit (f367)
 Motor rated speed (f417)
Return to default settings
Function
Default setting
0
Adjustment range
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10, 11: -
12: Number of starting clear
13: Default setting 2 (complete
initialization)
 Upper limit frequency (ul)
:50Hz
 Base frequency 2 (f170)
:50Hz
 VIB input point 2 frequency (f213):50Hz
 Automatic light-load high-speed operation
frequency (f330)
:50Hz
-1
 Communication command point 2 frequency
:1410 min
(f814)
D-10
E6581611
Default setting
0
:50Hz
:50Hz
:50Hz
:50Hz