Assign one type of function to an output terminal
Terminal
Title
symbol
RY-RC
Output terminal selection 1A
OUT
Output terminal selection 2A
FL
Output terminal selection 3
(A, B, C)
Note 2) When assigning 1 type of function to the RY-RC terminal, set only .
Leave parameter as the default setting ( = ).
Note 3) When assigning 1 type of function to the OUT terminal, set only .
Leave parameter as the default setting ( = ).
Assign two types of functions to the output terminal (RY-RC, OUT)
Terminal
Title
symbol
RY-RC
OUT
RY-RC,
OUT
Note 4) and are active only when = : Logic output (default).
Function is inactive when = : Pulse train output is set.
Function
Function
Output terminal
selection 1A
Output terminal
selection 1B
Output terminal
selection 2A
Output terminal
selection 2B
0: and
and
1: or
and
Output terminal logic
selection
2: and
or
3: or
or
G-7
Adjustment range
Default setting
4 (Low-speed detection
signal)
6 (Output frequency
0 - 255
attainment signal)
10 (Fault signal)
Adjustment range
4 (Low-speed
detection signal)
255 (Always ON)
0 - 255
6 (Output frequency
attainment signal)
255 (Always ON)
E6581611
Default setting
7
0