Pid Control Block Parameter List - PR 5350 Configuration Manual

Foundation fieldbus
Table of Contents

Advertisement

Rel.
Parameter
Index
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
5
MODE_BLK
6
BLOCK_ERR
7
PV
8
SP
9
OUT
10
PV_SCALE
11
OUT_SCALE
12
GRANT_DENY
13
CONTROL_OPTS
14
STATUS_OPTS
15
IN
16
PV_FTIME
17
BYPASS
18
CAS_IN
19
SP_RATE_DN
20
SP_RATE_UP
21
SP_HI_LIM
22
SP_LO_LIM
Rel.
Parameter
Index
23
GAIN

4.10 PID Control Block Parameter List

Description
The revision level of the static data associated with the func-
tion block. To support tracking changes in static para meter
attributes, the associated block's static revision parameter
will be incremented each time a static parameter attribute
value is changed. Also, the associated block's static revision
parameter may be incremented if a static para meter attribute
is written but the value is not changed.
The user description of the intended application of the block.
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
Contains the identification number of the plant unit. It helps
to identify the location (plant unit) of an event.
Contains the current mode and the permitted and normal
mode of the block.
This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
Either the primary analog value for use in executing the
function, or a process value associated with it. May also be
calculated from the READBACK value of an AO block.
The analog setpoint of this block.
The primary analog value calculated as a result of executing
the function.
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point to be used
in displaying the PV parameter and parameters which have
the same scaling as PV.
The high and low scale values, engineering units code, and
number of digits to the right of the decimal point to be used
in displaying the OUT parameter and parameters which have
the same scaling as OUT.
Options for controlling access of host computer and local
control panels to operating, tuning and alarm parameters of
the block.
Options which the user may select to alter the calculations
done in a control block.
Options which the user may select in the block processing of
status.
The primary input value of the block, required for blocks that
filter the input to get the PV.
Time constant of a single exponential filter for the PV, in
seconds.
The normal control algorithm may be bypassed through this
parameter. When bypass is set, the setpoint value (in percent)
will be directly transferred to the output. To prevent a bump
on transfer to/from bypass, the setpoint will automatically be
initialized to the output value or process variable, respective-
ly, and the path broken flag will be set for one execution.
This parameter is the remote setpoint value, which must
come from another Fieldbus block, or a DCS block through a
defined link.
Ramp rate at which downward setpoint changes are acted
on in Auto mode, in PV units per second. If the ramp rate is
set to zero, then the setpoint will be used immediately. For
control blocks, rate limiting will apply only in Auto. For output
blocks, rate limiting will apply in Auto, Cas, and RCas modes.
Ramp rate at which upward setpoint changes are acted on in
Auto mode, in PV units per second. If the ramp rate is set to
zero, then the setpoint will be used immediately. For control
blocks, rate limiting will apply only in Auto. For output blocks,
rate limiting will apply in Auto, Cas, and RCas modes.
The setpoint low limit is the lowest setpoint operator entry
that can be used for the block.
The setpoint high limit is the highest setpoint operator entry
that can be used for the block.
Description
Dimensionless value used by the block algorithm in calculat-
ing the block output.
Size
RO /
Type Store
byte
R/W
Un-
signed
SRC
2
RO
16
Octet
SRC
32
R/W
String
Un-
signed
SRC
2
R/W
16
Un-
signed
SRC
1
R/W
8
DS-69
Mix
4
Mix
Bit
D
2
RO
String
DS-65
D
5
RO
DS-65
N
5
R/W
DS-65
N
5
R/W
DS-68
SRC
11
R/W
DS-68
SRC
11
R/W
DS-70
SRC
2
R/W
Bit
SRC
2
R/W
String
Bit
SRC
2
R/W
String
DS-65
N
5
R/W
Float
SRC
4
R/W
Un-
signed
SRC
1
R/W
8
DS-65
N
5
R/W
Float
SRC
4
R/W
Float
SRC
4
R/W
Float
SRC
4
R/W
Float
SRC
4
R/W
Size
RO /
Type Store
byte
R/W
Float
SRC
4
R/W
Min. Max. Default
0
spaces
0
1
255
0
O/S
PV_SCALE
±10%
OUT_SCALE
±10%
0-100%
0-100%
0
0
Positive
0
1
2
0
Positive
+INF
Positive
+INF
PV_SCALE
100
±10%
PV_SCALE
0
±10%
Min. Max. Default
0
33

Advertisement

Table of Contents
loading