2.9.1 Linear interpolation linearisation, Description

LinType 1 = "Linearisation Table" generates a customer specific linear interpolation linearisation. Linear
interpolation linearisation can be used on mV, ohmic and potentiometer signals.The linear interpolation
linearisation is defined by straight lines drawn between the entered X / Y (input / output) coordinates.
The linearisation table must consist of 10 to 50 coordinate sets. The X values of the coordinates must
be entered in ascending order. The lowest and highest X values function as the lower and the upper lim-
it respectively. All X values must be entered as µV, Ohm or % for Voltage, Resistance or Potentiometer
measurements in that order. The table output will be converted to actual chosen PRMARY_VALUE_UNIT
(Example: 1000 / 3000 as X / Y values: output will read 3,00 if PRIMARY_VALUE_UNIT is set to "mV" and 1
mV is connected to input).

2.9.2 Linear Interpolation Linearisation, Parameter List.

Rel.
Parameter
Index
TAB_MIN_NUMBER
TAB_MAX_NUMBER
TAB_ACTUAL_NUMBER
TAB_X_Y_VALUE1
TAB_X_Y_VALUE2
TAB_X_Y_VALUE3
TAB_X_Y_VALUE4
TAB_X_Y_VALUE5
TAB_X_Y_VALUE6
TAB_X_Y_VALUE7
TAB_X_Y_VALUE8
TAB_X_Y_VALUE9
TAB_X_Y_VALUE10
TAB_X_Y_VALUE11
TAB_X_Y_VALUE12
TAB_X_Y_VALUE13
TAB_X_Y_VALUE14
TAB_X_Y_VALUE15
TAB_X_Y_VALUE16
TAB_X_Y_VALUE17
TAB_X_Y_VALUE18
TAB_X_Y_VALUE19
TAB_X_Y_VALUE20
TAB_X_Y_VALUE21
TAB_X_Y_VALUE22

2.9 PR_CUST_LIN Block Parameter List

Description
FF
34
Minimum number of linearisation points allowed (10)
35
Maximum number of linearisation points allowed (50)
36
Number of linearisation points in the linearisation table.
37
Linearisation x,y coordinate 1
38
Linearisation x,y coordinate 2
39
Linearisation x,y coordinate 3
40
Linearisation x,y coordinate 4
41
Linearisation x,y coordinate 5
42
Linearisation x,y coordinate 6
43
Linearisation x,y coordinate 7
44
Linearisation x,y coordinate 8
45
Linearisation x,y coordinate 9
46
Linearisation x,y coordinate 10
47
Linearisation x,y coordinate 11
48
Linearisation x,y coordinate 12
49
Linearisation x,y coordinate 13
50
Linearisation x,y coordinate 14
51
Linearisation x,y coordinate 15
52
Linearisation x,y coordinate 16
53
Linearisation x,y coordinate 17
54
Linearisation x,y coordinate 18
55
Linearisation x,y coordinate 19
56
Linearisation x,y coordinate 20
57
Linearisation x,y coordinate 21
58
Linearisation x,y coordinate 22
Size
RO /
Type Store
byte
R/W
Un-
signed
N
1
RO
8
Un-
signed
N
1
RO
8
Un-
signed
SRC
1
R/W
8
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Float
SRC
8
R/W
array
Min. Max. Default
10
50
11
0, 0
1000,
100
2000,
200
3000,
300
4000,
400
5000,
500
6000,
600
7000,
700
8000,
800
9000,
900
10000,
1000
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
0, 0
25

Advertisement

Table of Contents
loading

Table of Contents