Connecting a redundant power supply to 1 power supply unit
Use the left terminal block to connect the power supply. The terminal block is marked "X1":
L1 M1
Figure 6-2
Assignment of the LED display to the pins for redundant power supply with devices with one
power supply unit
● If the power supply fails at pins L1/M1, this is indicated by LED L1.
● If the power supply fails at pins L2/M2, this is indicated by LED L2.
Connecting a redundant power supply to 2 power supply units
To connect the power supplies, use pins L1/M1 of the left terminal block and pins L1/M1 of
the right terminal block. The left terminal block is marked "X1" and the right terminal block
"X2".
L1 M1
Figure 6-3
● If the power supply fails at pins L1/M1 of terminal block "X1", this is indicated by LED L1.
● If the power supply fails at pins L1/M1 of terminal block "X2", this is indicated by LED L2.