Daikin ERQ Service Manual page 106

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

Field Setting
(5) Thermostat Control
(5.1) X-control
When the DDC controller maintains level A for more than B minutes, and the thermostat is on,
thermo off is carried out for at least C minutes. After C minutes, thermostat on-conditions are
checked.
Mode n° setting
When the DDC controller reaches level D or higher (lower for heating) and the thermostat is off
for at least C minutes (refer to thermo off conditions), thermostat on is carried out for at least E
minutes.
Mode n° setting
96
Thermo off
Setting switch n°
51
8
6
9
Thermo on
Setting switch n°
51
7
5
b
Setting position n°
00
level A = 1 (cooling)
01
level A = 1 or 2 (cooling)
00
B = 3 min, C = 3 min
01
B = 5 min, C = 3 min
02
B = 7 min, C = 3 min
03
--
04
B = 3 min, C = 5 min
05
B = 5 min, C = 5 min
06
B = 7 min, C = 5 min
07
--
08
B = 3 min, C = 10 min
09
B = 5 min, C = 10 min
10
B = 7 min, C = 10 min
00
level A = 5 (heating)
04
level A = 4 or 5 (heating)
Setting position n°
00
D = level 1 (cooling)
02
D = level 2 (cooling)
04
D = level 3 (cooling)
06
D = level 4 (cooling)
08
D = level 5 (cooling)
00
E = 3 min
01
E = 5 min
02
E = 10 min
00
D = level 1 (heating)
01
D = level 2 (heating)
02
D = level 3 (heating)
03
D = level 4 (heating)
04
D = level 5 (heating)
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Setting
Setting
Test Operation