Field Setting
3.2
Field Setting from Outdoor Unit
3.2.1 Setting by Dip Switches
The following field settings are made by dip switches on PC board.
No.
DS1-1
DS1-2
D-box: cool/heat selection by remote controller
F-box: no remote controller
Cool/heat selector connection procedure
•
100
Dipswitch
Setting
ON
OFF (Factory set)
ON
OFF (Factory set)
-> cool/heat selection through ABC-contact
Set the remote controller only when changing over the operation mode between cooling and
heating using the remote controller installed in the outdoor.
Connect the cool/heat selector (optional accessory) to the terminals (A, B and C) on the
outdoor X2M Terminal board (A, B and C).
Set the cool/heat selector switch DS1-1 from "OFF" (which is selected at the factory before
shipment) to "ON".
A1P
DS1-1
switch knob
Setting item
Cool / Heat
Used to set cool / heat change over setting by remote
change over
controller equipped with outdoor unit. (Note 1)
setting
Not used
Do not change the factory settings.
DS1 1 2
X2M
A B C
A B C
Cool/heat
selector (option KRC 19-26 A6)
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Description
Test Operation