Daikin ERQ Service Manual page 108

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

Field Setting
Mode n° setting
(6.2) Y-control
Since there is no external input to change the T
local setup by means of the Daikin remote controller (during installation).
Cooling: T
Heating: T
Mode n° setting
(7) Renewal of Target Refrigerant Temperature (X-control)
When a level of the main pcb is updated, the T
simultaneously, otherwise the T
When the DDC level remains constant for A seconds, a level update is executed in the main
pcb.
Mode n° setting
98
Heating: Upper & lower limit of T
Setting switch n°
51
0
setting
e
setting
c
Setting switch n°
23 (13)
1
2
Setting switch n°
20 (10)
4
can be chosen
c
Setting position n°
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
/T
value, their values can only be changed by
e
c
Setting position n°
01
T
02
T
03
T
04
T
05
T
06
T
07
T
08
T
01
T
02
T
03
T
04
T
05
T
06
T
07
T
/T
value of the outdoor is updated
e
c
/T
value remains constant.
e
c
Setting position n°
01
A = 60 sec
02
A = 120 sec
03
A = 180 sec
04
A = 240 sec
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Setting
Lower limit T
Upper limit T
c
(°C)
(°C)
30
55
35
55
40
55
43
55
30
50
35
50
40
50
43
50
30
49
35
49
40
49
43
49
30
45
35
45
40
45
43
45
Setting
= 5°C
e
= 6°C
e
= 7°C
e
= 8°C
e
= 9°C
e
= 10°C
e
= 11°C
e
= 12°C
e
= 43°C
c
= 44°C
c
= 45°C
c
= 46°C
c
= 47°C
c
= 48°C
c
= 49°C
c
Setting
Test Operation
c

Hide quick links:

Advertisement