Functional Parts Layout; Erq 100/125/140 A7V1B - Daikin ERQ Service Manual

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

Functional Parts Layout

2. Functional Parts Layout

2.1

ERQ 100/125/140 A7V1B

Birds-eye view
Y2S SOLENOID VALVE
(CONNECTOR COLOR : BLACK)
(HIGH VOLTAGE)
R5T THERMISTOR (SUCTION 2)
(MARKING COLOR : GREEN)
S1PH PRESSURE SWITCH LEAD WIRE
(CONNECTOR COLOR : WHITE)
R2T THERMISTOR (DISCHARGE)
(CONNECTOR COLOR : BLUE)
E1HC CRANKCASE HEATER LEAD WIRE
(CONNECTOR COLOR : GRAY)
(HIGH VOLTAGE)
18
S1NPH PRESSURE SENSOR (HIGH) LEAD WIRE
(CONNECTOR COLOR : RED)
(LOW VOLTAGE)
Y1S 4 WAY VALVE LEAD WIRE
(CONNECTOR COLOR : BLUE)
(HIGH VOLTAGE)
R3T THERMISTOR (SUCTION 1)
(MARKING COLOR : RED)
S1NPL PRESSURE SENSOR (LOW)
(CONNECTOR COLOR : BLUE)
Y3S SOLENOID VALVE LEAD WIRE
(CONNECTOR COLOR : PINK)
(HIGH VOLTAGE)
Y1E ELECTRIC EXPANSION VALVE
(CONNECTOR COLOR : WHITE)
Y3E ELECTRIC EXPANSION VALVE
(MARKING COLOR : BLUE)
R7T THERMISTOR (LIQUID PIPE 1)
(MARKING COLOR : BLUE)
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Refrigerant Circuit

Hide quick links: