Model Names of Outdoor Units, Control Box and Expansion Valve Kit
1.3
Expansion Valve Kit
Outlook
Expansion valve kit installation drawing:
Model name
Limits for outdoor unit (expansion valve kit).
Outdoor unit (class)
Depending on the heat exchanger, a connectable EKEXV (expansion valve kit) must be
selected to these limitations.
EKEXV class
Saturated suction temperature (SST) = 6°C, SH (superheat) = 5 K, air temperature = 27°C DB /
19°C WB.
4
100
EKEXV63~125
125
EKEXV63~140
140
EKEXV80~140
Allowed heat exchanger volume (dm
Minimum
63
1.66
80
2.09
100
2.65
125
3.31
140
4.13
EKEXV kit
3
) Allowed heat exchanger capacity (kW)
Maximum
Minimum
2.08
2.64
3.30
4.12
4.62
: http://splitoff.ru/tehn-doc.html
ESIE09-05
Maximum
6.3
7.8
7.9
9.9
10.0
12.3
12.4
15.4
15.5
17.6
General Information