Field Setting; Field Setting From Remote Controller - Daikin ERQ Service Manual

Erq 100/125/140 a7v1b (outdoor unit) ekeqd/f/mcbv3 (control box) ekexv 50/63/80/100/125/140 (expansion valve kit)
Hide thumbs Also See for ERQ:
Table of Contents

Advertisement

Field Setting

3. Field Setting

3.1

Field Setting from Remote Controller

Individual function of AHU can be changed from the remote controller. At the time of installation
or after service inspection / repair, make the local setting in accordance with the following
description.
Wrong setting may cause malfunction.
3.1.1 Wired Remote Controller
BRC1D528
1. When in the normal mode, press the "
2. Select the desired MODE NO. with the "
3. Push the "
4. Push the "
5. Push the "
6. Push the "
Notes :
1. Do not make any settings not given in the table.
2. Not displayed if the AHU is not equipped with that function.
3. When returning to the normal mode, "88" may be displayed in the LCD in order for the
92
UNIT NO.
FIRST
CODE NO.
SECOND
CODE NO.
3
1
6
FIELD SET MODE is entered.
" upper button and select FIRST CODE NO.
" lower button and select the SECOND CODE NO.
" button once and the present settings are SET.
" button to return to the NORMAL MODE.
remote controller to initialize itself.
UNIT No.
GR OUP
SETTING
5
4
2
" button for a minimum of four seconds, and the
" button.
: http://splitoff.ru/tehn-doc.html
ESIE09-05
MODE NO.
FIELD
SET
MODE
Test Operation