Control Specification
3.3.4
3-Minute Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting.)
3.3.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting.)
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
3.4
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail
Divide the Zone
Management within the Zones
34
88
64
48
240
360
180
Stop zone
A˚C
Drooping zone
B˚C
Keep zone
Heat exchanger
thermistor temperature
Zone
Stop zone
Drooping zone
Keep zone
Return zone
C˚C
D˚C
Up zone
E˚C
Return zone
(R6167)
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Start the timer, and the frequency will be drooping.
Keep the upper limit of frequency.
Cancel the upper limit of frequency.
A
110
B
105
C
101
D
99
E
97
Control contents
Function and Control
SiBE04-809
Need help?
Do you have a question about the ARXG35E3V1B and is the answer not in the manual?
Questions and answers