Programme Dry Function - Daikin ARXG35E3V1B Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for ARXG35E3V1B:
Table of Contents

Advertisement

SiBE04-809
1.5

Programme Dry Function

Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and airflow volume, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
In Case of
The microcomputer automatically sets the temperature and fan settings. The difference
between the room temperature at startup and the temperature set by the microcomputer is
Inverter Units
divided into two zones. Then, the unit operates in the dry mode with an appropriate capacity for
each zone to maintain the temperature and humidity at a comfortable level.
Function and Control
Room temperature at
startup
24ºC or more
Room temperature at
23.5ºC
18ºC
17.5ºC
Zone B
Y
Zone A = Thermostat OFF
Set temperature
Thermostat OFF point
X
startup
18ºC
Zone C = Thermostat ON
Main Functions
Thermostat ON point
Y
X
X
2.5ºC
Y + 0.5ºC (zone B)
continues for 10 min.
X
X
2.0ºC
Y + 0.5ºC (zone B)
continues for 10 min.
X
0.5ºC = 17.5ºC
X
2.0ºC
Y + 0.5ºC (zone B)
continues for 10 min.
Z
Zone B
+0.5ºC
(R6841)
Z
0.5ºC
or
0.5ºC
or
or
19

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ARXG35E3V1B and is the answer not in the manual?

Questions and answers

Table of Contents