EXPERT MODE PARAMETERS

In the following parameter table:
'•'
Indicates parameters that can be changed during operation.
œœœ
'
' Indicates that the value of this factory setting depends on the rating of the inverter.
Parameter
Operating display
13-8
Function
Range
[default]
-
ECO REFERENCE MANUAL
Description / Notes
(output frequency) Hz
Displays the output selected by P001 (an
Expert mode parameter).
Display selection via P001:
0 = Output frequency (Hz)
1 = Frequency setpoint (i.e. speed at
which inverter is set to run) (Hz)
2 = Motor current (A)
3 = DC-link voltage (V)
4 = Motor torque (% nominal)
5 = Motor speed (rpm)
6 = USS serial bus status
7 = PID Feedback signal (%)
8 = Output voltage (V)
The default setting (0) displays the inverter
output frequency. If the inverter is in stand-
by mode, the flashing display will alternate
between the setpoint frequency and actual
output frequency, which will be 0 Hz when
not being run.
In the event of a failure, the relevant fault
code (Fnnn) is displayed.