Output Reactors (Chokes) - Siemens Midimaster Eco Reference Manual

Hvac-frequency inverter for fans and pumps from 0.75 kw to 315 kw
Hide thumbs Also See for Midimaster Eco:
Table of Contents

Advertisement

OUTPUT REACTORS (CHOKES)

Output reactors are fitted to the output terminals (U, V & W) of the inverter to allow operation with long
motor cables. The inductance of the output reactor compensates for the stay phase-to-phase and
phase-to-earth capacitance of the motor cable.
As the motor cable length is increased the total stray capacitance of the motor cable also increases.
This stray cable capacitance combined with the residual voltage spikes on the inverter output (caused
by the Pulse Wide Modulation (PWM) switching of the inverter's IGBT output devices) has the effect of
causing current spikes to flow back to the inverter. These current spikes may cause nuisance tripping
of the inverter which can be prevented by the installation of an output reactor.
The recommended motor cable lengths for screened and unscreened cables when output reactors are
fitted are shown within the table below:
Maximum Cable Length (m)
for MICROMASTER Eco & MIDIMASTER Eco
Inverter
Standard (no output
Rating
reactor fitted)
(kW)
Screened
Cable
Up to 1.5kW
80
2.2 to 3
135
4
200
5.5
200
7.5
200
11*
50
15*
50
18.5*
50
22*
50
30*
50
37*
50
45*
50
55
300
75
300
90
200
15-28
Output Reactor
Unscreened
Screened Cable
Cable
One
Reactor
Fitted
110
150
165
200
200
250
200
250
200
250
50
100
50
100
50
100
50
100
50
100
50
100
50
100
300
300
300
300
300
300
ECO REFERENCE MANUAL
Output Reactor
Fitted
Unscreened Cable
Two Reactors
One
Fitted in
Reactor
Series
Fitted
200
180
250
250
300
300
300
300
300
300
150
150
150
150
150
150
150
150
150
150
150
150
150
150
400
400
400
400
400
400
Fitted
Two
Reactors
Fitted in
Series
250
300
350
350
350
200
200
200
200
200
200
200
500
500
500