ECO REFERENCE MANUAL
Parameter
Access to expert mode
PID closed loop mode
P gain
I gain
D gain
Integral gain scaling
Transducer filtering
Integral capture range (%)
Transducer type
Transducer reading (%)
(unscaled)
0% setpoint
100% setpoint
Function
Range
[default]
0 or 1
0 - 1
[0]
0.0-999.9
[1.0]
0.00-99.9
[0]
0.0-999.9
[0]
1 - 2400
[1]
0 - 255
[0]
0 - 100
[100]
0 - 1
[0]
0.00-
100.00
[-]
0.0 -
100.00
[0.0]
0.0 -
100.00
[100.00]
Description / Notes
This value enables or disables access to
Expert mode parameters.
0 =
Normal mode parameter values only
can be changed.
1 =
Expert mode parameter values can
be changed in addition to the Normal mode
parameters.
It is possible to reset all parameter values to
their factory default settings using expert
parameter P944.
0 = Normal operation (closed loop process
control disabled).
1 = Closed loop process control using
analogue input 2 as feedback.
Proportional gain.
Integral gain.
Derivative gain.
The integral action time is multiplied by this
value
0 = Filter off.
1 - 255 = Low pass filtering applied to
transducer.
Percentage error above which integral term
is reset to zero.
0 = An increase in motor speed causes an
increase in transducer voltage/current
output.
1 = A increase in motor speed causes an
decrease in transducer voltage/current
output.
Read-only. Value is a percentage of full
scale of the selected signal input
(i.e. 10 V or 20 mA).
Value of P210 to be maintained for 0%
setpoint.
Value of P210 to be maintained for 100%
setpoint.
13-27