EG
EXAMPLE 2.
ANALOG CURRENT SETPOINT AND RUN/STOP VIA TERMINALS
A pump is to be speed controlled using an external 4 - 20 mA current signal
All settings based on factory settings with the following exceptions :
P006 = 1
P007 = 0
P023 = 1
A
B
11-2
PARAMETER CHANGES FROM FACTORY DEFAULTS
SETTING
SELECT ANALOG SET POINT
SELECT RUN/STOP FROM TERMINALS
SELECT 4 - 20 mA RANGE
L1
L2
L3
N
PE
FUSES
MAIN CONTACTOR
L1
L2
L3
MICROMASTER Eco
MIDIMASTER Eco
U
V
W
M
ITEM
RUN/STOP SWITCH
4 - 20 mA SPEED SETTING SIGNAL
DESCRIPTION
FAULT CONTACT
19
20
CLOSED = HEALTHY
9
5
3
4
PUMP
DESCRIPTION
ECO REFERENCE MANUAL
A
4-20mA
B
DC
DIP SWITCHES