TECHNICAL FEATURES

Inverter
MICROMASTER Eco
Input Voltage
3 AC 208 - 240V±10%
3 AC 380 – 480 / 500V±10%
Power Ranges
3 AC 208-240V
0.75kW - 4.0kW
3 AC 380-500V
1.1kW - 7.5kW
3 AC 525-575V
-
Protection Level
IP20 / NEMA1
EMC conformance
EN55011 Class A
3 AC 208-240V
Footprint Filter
3 AC 380-460V
Integrated or Footprint Filter
3 AC 525-575V
not available
EMC conformance
EN55011 Class B
3 AC 208-240V
Footprint Filter
3 AC 380-460V
Footprint Filter
3 AC 525-575V
not available
Temperature
0 - 50
Range
Control Method
Energy Control Optimisation (Eco) Mode or Multi-motor Mode.
Protection Features
Undervoltage, Overvoltage, Overload, Short-Circuit, Earth Fault, Motor Pull-
out, Motor Overtemperature, Drive Overtemperature
Maximum Motor
See section 14
Cable Length
Overload Capability
150% for 60 sec
Digital Inputs
6 configurable
Fixed Frequencies
8
Relay Outputs
2 configurable (230V AC/1.0A)
Analogue Inputs
2
Analogue Outputs
1 configurable
Serial Interface
RS485
Dynamic Braking
Compound Braking
/DC Injection Braking
Process Control
PID
5-2
0
C
ECO REFERENCE MANUAL
MIDIMASTER Eco
3 AC 208 - 240V±10%
3 AC 380V - 460 / 480 / 500V±10%
3 AC 525V - 575V±15%
5.5kW - 45kW
(1.1kW - 45kW) IP56
11kW - 315kW
(3kW - 90kW) IP56
4kW - 45kW
(4kW - 45kW) IP56
IP20 / IP21 / NEMA1 or IP56 / NEMA 4/12
or
IP20 / NEMA1 with integrated Class A
EMC filter
Integrated or external Filter
Integrated or external Filter
not available
External Filter
External Filter
not available
0
0 - 40
C See Section 14 for derating at
higher temperatures
See Section 14
110% for 60 sec
6 configurable
8
2 configurable (230V AC/1.0A)
2
2 configurable
Compound Braking
/DC Injection Braking
PID