Siemens Midimaster Eco Reference Manual page 106

Hvac-frequency inverter for fans and pumps from 0.75 kw to 315 kw
Hide thumbs Also See for Midimaster Eco:
Table of Contents

Advertisement

Value
Function of P051 to P055 and P356
0
Input disabled
1
On right
4
OFF2
5
OFF3
6
Fixed frequencies 1-6
9
Start / Stop command selection from keypad
or digital terminals (for USS communication
operation P910 = 1 or 3)
10
Fault reset
11
Increase frequency*
12
Decrease frequency*
13
Switch between analogue input frequency
setting and digital/keypad frequency setting
14
Disable the ability to change parameters
18
Fixed frequencies 1-6, but input high will also
request RUN when P007 = 0
19
External trip
22
Download parameter set 0 from Ope***
23
Download parameter set 1 from OPe***
24
Switch analogue setpoint
*
Only effective when P007 = 0.
**
Not available on P051, P052 or P356.
***
The motor must be stopped before downloading begins.
Downloading takes approx. 30 seconds.
13-16
ECO REFERENCE MANUAL
Function,
Function,
low state
high state
(0V)
-
-
Off
On right
OFF2
On
OFF3
On
Off
On
Local Keypad
Digital Terminal Start
Start / Stop
/ Stop (or USS
communication
control)
Off
Reset on rising edge
Off
Increase
Off
Decrease
Analogue
Keypad / Digital
setpoint
setpoint
'P' enabled
'P' disabled
Off
On
Off
On
Off
Download
Off
Download
Analogue input
Analogue input 2
1 active
active
(>10V)