Siemens Midimaster Eco Reference Manual page 160

Hvac-frequency inverter for fans and pumps from 0.75 kw to 315 kw
Hide thumbs Also See for Midimaster Eco:
Table of Contents

Advertisement

ECO REFERENCE MANUAL
Maximum Cable Length (m)
for MICROMASTER Eco & MIDIMASTER Eco
Inverter
Standard (no output
Rating
reactor fitted)
(kW)
Screened
Cable
110
200
132
200
160
200
200
200
250
200
315
300
*It is often a simpler and more economic connection solution to select an Eco inverter rating
which is one kW rating larger rather than to fit an output reactor, see section 14 for de-rating
information.
The maximum switching frequency must be limited to 2kHz for iron cored reactors and 4Hz for
ferrite cored reactors.
For multi-motor connection to a single inverter the total motor cable length is the sum of the
individual motor cable lengths.
Output Reactor
Unscreened
Screened Cable
Cable
One
Reactor
Fitted
300
300
300
300
300
300
300
300
300
350
300
350
Output Reactor
Fitted
Unscreened Cable
Two Reactors
One
Fitted in
Reactor
Series
Fitted
400
400
400
400
400
400
400
400
450
400
450
400
Fitted
Two
Reactors
Fitted in
Series
500
500
500
500
550
550
15-29