ECO REFERENCE MANUAL
Parameter
Analogue input 2 type
•
Digital input 6 configuration
Inertia compensation
Direct input/output functions
•
Analogue input 1 voltage
(V)
Analogue output 1 current
•
(mA)
Function
Range
[default]
0 - 2
[0]
0 - 24
[6]
0.1-20.0
[1.0]
0 - 7
[0]
0.0 - 10.0
[-]
0.0 - 20.0
[0.0]
Description / Notes
Sets analogue input type for analogue input
2, in conjunction with the settings of the DIP
selector switches 4 and 5 ( see the DIP
Selector Switches figure in this section) :
0 = 0 V to 10 V/ 0 to 20 mA Unipolar input
1 = 2 V to 10 V/ 4 to 20 mA Unipolar input
2 = 2 V to 10 V/ 4 to 20 mA Unipolar input
with controlled start / stop when using
analogue input control.
Setting P323 = 2 will not work unless the
inverter is under full local control (i.e. P910 =
0 or 4) and V ≥ 1 V or 2mA.
WARNING:
The inverter will automatically start when
voltage goes above 1V. This equally applies
to both analogue and digital control (i.e.
P006 = 0 or 1)
Control function selection, DIN 6
See P051 - P055 for description.
To ensure reliable starting on the fly this
term may need to be adjusted dependent on
load inertia. For high inertia loads increase
the setting until reliable re-start occurs
following short mains breaks.
Allows direct access to the relay outputs and
the analogue output via the serial link (USS):
0 = Normal operation
1 = Direct control of relay 1
2 = Direct control of relay 2
3 = Direct control of relay 1 and relay 2
4 = Direct control of analogue output 1 only
5 = Direct control of analogue output 1 and
relay 1
6 = Direct control of analogue output 1 and
relay 2
7 = Direct control of analogue output 1,
relay 1 and relay 2
Read only. Displays the analogue input 1
voltage (approximate).
Allows direct control of the output current if
P720 = 4, 5, 6 or 7.
13-29