Configuration of User Administration

To branch to the wizard to configure user administration, click the appropriate icon
in the left-hand box of the screen. All the information entered in this wizard is
stored in the file system of the CP 243-1 IT in a file with the ending .udb when the
configuration is loaded to the S7-200 system.
Configuring the users
Using the screens which appear, you can configure up to 8 users. You must assign
a user identifier, a password and user-specific access rights to each user.
Make sure that the user identifiers are unique.
As soon as you have configured the desired number of users, you can click "Next"
to conclude user configuration.
Then you can either branch to another wizard or conclude the configuration of the
CP 243-1 IT by clicking "Finish".
4.3.3

Configuration of the E-Mail Functions

To branch to the wizard to configure the e-mail functions, click the appropriate icon
in the left-hand box of the screen. All the information entered in this wizard is
stored in the file system of the CP 243-1 IT in a file with the ending .edb when the
configuration is loaded to the S7-200 system.
Configuring the e-mail address and the e-mail server to be used
In the first screen of the e-mail wizard, assign an e-mail address to your S7-200
system. The e-mail address specified here will be entered as the sender address in
all transmitted e-mails.
Then choose an e-mail server to which your CP 243-1 IT is to transmit the e-mails
to be sent. Enter the IP address and the port of this e-mail server. An e-mail server
can usually be accessed via port 25. This port is preset. If the e-mail server you
specified uses a different port, enter this port in the appropriate box.
For reliability's sake, you can enter a second e-mail server. The CP 243-1 IT at-
tempts to send an e-mail to the e-mail server specified first. If this server cannot be
reached (e.g., due to a network malfunction), the CP 243-1 IT then attempts to
send the -mail to the second e-mail server. If the second e-mail server also cannot
be reached, the CP 243-1 IT terminates its attempts to send the e-mail and gener-
ates an appropriate error message.
Configuring the e-mails
The next screen is used to configure the e-mails. The address to which the e-mail
is to be sent must be entered in this screen for every e-mail which is to be sent
from the CP 243-1 IT. In addition, a second recipient of a copy of the e-mail can be
specified. The subject can also be entered here.
CP 243-1 IT
J31069-D0429-U001-A0-7618
Configuration
65