Diagnosis
Error Word
Hex
Dec
16#00B3
179
The administrator password
check failed or no password
was specified.
16#00B7
183
The administrator password is
too short.
16#00BB
187
Wrong IDB format
16#00BD
189
Initialization of the file system
failed.
16#00BF
191
System files could not be set up
in the file system.
16#00F0
240
The S7-200 CPU failed to rec-
ognize the CP 243-1 IT.
16#00F1
241
The address of the output byte
via which the CP 243-1 IT is
supposed to be accessible ac-
cording to the configuration is
not compatible with the current
position of the CP 243-1 IT on
the S7-200 system.
16#0100
256
Time was exceeded on the
backplane bus.
to
to
16#0108
264
16#8080
32896
CP 243-1 IT not yet completely
booted.
Table 30
118
Error Byte
Prepare configuration with
STEP 7 Micro/WIN 32.
Prepare configuration with
STEP 7 Micro/WIN 32.
Prepare configuration with
STEP 7 Micro/WIN 32.
Delete files from the file sys-
tem.
Delete files from the file sys-
tem.
Check configuration and
setup of the S7-200 system.
Check configuration and
setup of the S7-200 system
Automatic restart
If necessary, check 24 V sup-
ply.
Error messages in word format
Reaction/Correction
J31069-D0429-U001-A0-7618
03/03
Transfer Rou-
tine
Byte
Return
Offset
Value
in SM
(ETHx_)
Area
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
_CTRL
_CTRL
20, 21
_CTRL
20, 21
_CTRL