Error Byte
Hex
Dec
16#05
5
The connection was terminated or
an attempt was made to execute a
read/write job on a channel which
was not ready.
The connection could not be estab-
lished or was terminated. Or the e-
mail configuration file on the CP
243-1 IT was changed. Or an at-
tempt was made to execute a job
and the e-mail service was not cor-
rectly parameterized.
The connection could not be estab-
lished or was terminated. Or the
FTP configuration file on the CP
243-1 IT was changed. Or an at-
tempt was made to execute a job
and the FTP client service was not
correctly parameterized.
The FTP connection was termi-
nated.
The connection could not be estab-
lished or was terminated. Or an at-
tempt was made to execute a job
and the HTTP server was not cor-
rectly parameterized.
16#06
6
The response packet contains logi-
cal errors.
16#07
7
The read job failed.
16#08
8
The write job failed.
16#09
9
Channel not configured
16#0A 10
The channel is configured as
SERVER but an attempt was made
to trigger a read/write job.
CP 243-1 IT
J31069-D0429-U001-A0-7618
Description
Reaction/Correction
Check connection path to the
communication partner or con-
figuration of the communication
partner.
Check connection path to the
communication partner.
Check .edb file on the CP 243-1
IT for uniqueness and com-
pleteness.
Check connection path to the
communication partner.
Check .fdb file on the CP 243-1
IT for uniqueness and com-
pleteness.
Check connection path to the
communication partner.
Check FTP server configuration
for completeness.
Check connection path to the
communication partner.
Check HTTP server configura-
tion for completeness.
A new read/write job can be
triggered.
Check the configuration.
A new read/write job can be
triggered.
The parameters of the read job
should be checked.
A new read/write job can be
triggered.
The parameters of the write job
should be checked.
A new read/write job with other
parameters can be triggered.
A new read/write job with other
parameters can be triggered.
Diagnosis
Transfer Rou-
tine
Byte
Return
Offset
Value
in SM
(ETHx_)
Area
25 - 32 _XFR
34
_EMAIL
35
_FTPC
36
37
25 - 32
_XFR
34
_EMAIL
35
_FTPC
25 - 32 _XFR
25 - 32 _XFR
25 - 32
_XFR
34
_EMAIL
35
_FTPC
25 - 32 _XFR