Siemens SIMATIC NET CP 243-1 IT Technical Manual page 117

Communications processor for industrial ethernet and information technology
Table of Contents

Advertisement

03/03
Error Word
Hex
Dec
16#003A
58
The module name for the CP
243-1 IT was changed in the
configuration.
16#003B
59
The configuration has an invalid
IP address.
16#003C
60
The configuration has an invalid
gateway address.
16#003D
61
The configuration has an invalid
value in the Keep Alive parame-
ter.
16#003E
62
No valid configuration received
from memory or S7-200 CPU or
via BOOTP
16#0042
66
The NDB contains syntax mis-
takes in the read/write jobs or
lengths.
16#0093
147
The BOOTP job failed.
16#0094
148
The reply of the BOOTP server
contains invalid data.
16#0095
149
The TCP/IP stack did not ac-
cept the specified monitoring
time (Keep Alive).
16#0096
150
The TCP/IP stack did not ac-
cept the IP address specified
for a client.
16#0097
151
The TCP/IP stack did not ac-
cept the specified subnet mask.
16#0098
152
The TCP/IP stack did not ac-
cept the specified gateway ad-
dress.
16#00B0
176
The IDB contains invalid val-
ues.
16#00B1
177
The CRC check of the IDB
failed.
16#00B2
178
No administrator name is speci-
fied in IDB.
CP 243-1 IT
J31069-D0429-U001-A0-7618
Error Byte
Check the configuration.
Check the configuration.
Check the configuration.
Check the configuration.
Cyclic attempt to obtain a
valid configuration either from
the memory of the S7-200
CPU or via a BOOTP server
Check the configuration.
Automatic restart
Automatic restart
Automatic restart
Automatic restart
Automatic restart
Automatic restart
Prepare configuration with
STEP 7 Micro/WIN 32.
Prepare configuration with
STEP 7 Micro/WIN 32.
Check the user program to
see whether configuration
data were accidentally over-
written.
Prepare configuration with
STEP 7 Micro/WIN 32.
Reaction/Correction
Diagnosis
Transfer Rou-
tine
Byte
Return
Offset
Value
in SM
(ETHx_)
Area
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
20, 21
_CTRL
117