Rack Stability

Rack stabilizers are required when you have less than four racks bayed together.
NOTE:
Rack stability is of special concern when equipment is routinely installed, removed, or
accessed within the rack. Stability is addressed through the use of leveling feet, baying kits, fixed
stabilizers, and/or ballast. Use baying kits to bay Intelligent racks to Intelligent racks of the same
height. In all cases, a rack cannot be bayed with another rack of a different height.
For information about best practices for racks or grounding the racks using a rack ground bonding
kit, your service provider can refer to:
HP Rack Options Installation Guide
http://www.hpe.com/support/Intelligent_Series_Rack_Manuals

Environmental Specifications

Heat Dissipation Specifications and Worksheet

Enclosure Type
16 GB CPU
32 GB CPU
48 GB CPU
VIO enclosure
G6 Storage CLIM
G6 IP or Telco CLIM
Gen8 Storage CLIM
Gen8 Networking
CLIM, 5 copper ports
(IP or Telco)
Gen8 Networking
CLIM, 3 copper
ports/2 optical ports
(IP or Telco)
Gen9 Networking
CLIM, 5 copper ports
(IP or Telco)
Gen9 Networking
CLIM, 3 copper
ports/2 optical ports
(IP or Telco)
D2700 SAS disk
enclosure (no disks)
D3700 SAS disk
enclosure (no disks)
SAS 2.5 in. 10k rpm
disk drive
SAS 2.5 in. 15k rpm
disk drive
Number Installed
Unit Heat
(BTU/hour) Typical
924
938
952
894
461
444
419
399
419
443
461
256
256
17
14
Unit Heat
Total (BTU/hour)
(BTU/hour)
Maximum
1212
1240
1268
1112
768
682
699
692
716
614
631
427
427
30
24