Enclosure Type
Gen9 Storage CLIM
G6 IP or Telco CLIM
Gen8 Networking CLIM 5
copper ports (IP or Telco)
Gen8 Networking CLIM 3
copper/2 optical ports (IP or
Telco)
Gen9 Networking CLIM, 5
copper ports (IP or Telco)
Gen9 Networking CLIM, 3
copper/2 optical ports (IP or
Telco)
D2700 SAS disk enclosure
(no disks)
D3700 SAS disk enclosure,
empty
SAS disk drive 10k rpm
SAS disk drive 15k rpm
200GB SAS 2.5" SSD, Gen1
200GB SAS 2.5" SSD, Gen2
400GB SAS 2.5" SSD
Rack-mounted system
console (NSCR212)
Rack-mounted keyboard and
monitor
Maintenance switch (Ethernet)
2
1
One of the plugs for an enclosure must be connected to one of the left-side extension bars and the other one connected
to one of the right-side extension bars. PDUs must be supplied from separate branch circuits.
2
Maintenance switch has only one plug. If a UPS is installed in the rack, the maintenance switch plug must be connected
to the extension bars on the right side of the rack.
48
System Installation Specifications for NS2300 Systems
AC Power Lines per
1
Enclosure
2
2
2
2
2
2
-
-
-
-
-
1
1
1
Typical Power
Consumption (Watts)
140
130
117
123
130
135
75
75
5
4
6
6
6
105
28
20
Maximum Power
Consumption (Watts)
190
200
203
210
180
185
125
125
9
7
6
6
6
115
28
20
Need help?
Do you have a question about the Integrity NonStop i NS2300 and is the answer not in the manual?
Questions and answers