Vega VEGAFLEX 61 Operating Instructions Manual page 58

Level sensor
Hide thumbs Also See for VEGAFLEX 61:
Table of Contents

Advertisement

10 Supplement
Status
Description according to Pro-
code
fibus standard
0x0C
bad - sensor failure
0x10
bad - sensor failure
0x1f
bad - out of service constant
0x44
uncertain - last unstable value
0x48
uncertain substitute set
0x4c
uncertain - initial value
0x51
uncertain - sensor; conversion
not accurate - low limited
0x52
uncertain - sensor; conversion
not accurate - high limited
0x80
good (non-cascade) - OK
0x84
good (non-cascade) - active
block alarm
0x89
good (non-cascade) - active ad-
visory alarm - low limited
0x8a
good (non-cascade) - active ad-
visory alarm - high limited
0x8d
good (non-cascade) - active cri-
tical alarm - low limited
0x8e
good (non-cascade) - active cri-
tical alarm - high limited
58
Possible cause
l Hardware error
l Converter error
l Leakage pulse error
l Trigger error
l Measured value generation error
"Out of Service" mode switched on
Failsafe replacement value (Failsafe-Mode = "Last value" and
already valid measured value since switching on)
l Switch on simulation
l Failsafe replacement value (Failsafe-Mode = "Fsafe value")
Failsafe replacement value (Failsafe-Mode = "Last valid value" and
no valid measured value since switching on)
Sensor value < lower limit
Sensor value > upper limit
OK
Static revision (FB, TB) changed (10 sec. active, after the parameter
of the static category was written)
Lo-Alarm
Hi-Alarm
Lo-Lo-Alarm
Hi-Hi-Alarm
VEGAFLEX 61 • Profibus PA