Vega VEGAFLEX 61 Operating Instructions Manual page 29

Level sensor
Hide thumbs Also See for VEGAFLEX 61:
Table of Contents

Advertisement

Sensor-TAG
Gating out of false sig-
nals
VEGAFLEX 61 • Profibus PA
6 Set up with the indicating and adjustment module PLICSCOM
Linearisation curve
linear
Enter the requested parameters via the appropriate keys, save your
settings and jump to the next menu item with the [->] key.
Caution:
Note the following, if VEGAFLEX 61 is used as part of an overfill
protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer
compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.
In this menu item you can enter an unambiguous designation for the
sensor, e.g. the measurement loop name or the tank or product
designation. In digital systems and in the documentation of larger
plants, a singular designation should be entered for exact identification
of individual measuring points.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is finished and you can now
jump to the main menu with the [ESC] key.
High sockets or vessel installations, such as e. g. struts or agitators as
well as buildup and weld joints on the vessel walls, cause interfering
reflections which can impair the measurement. A false echo storage
detects and marks these false echoes, so that they are no longer taken
into account for the level measurement. A false echo memory should
be created with low level so that all potential interfering reflections can
be detected.
Gating out of false signals
Change now?
Proceed as follows:
1
Move from the measured value display to the main menu by
pushing [OK].
29