8 Maintenance and fault rectification
Shorten cable/rod
40
Fig. 21: Exchanging the cable or rod
Information:
Please keep the stated torque so that the max. tensile strength
remains.
The cable and rod of the probe can be shortened by any amount.
1
Cable: loosen the three pins on the gravity weight (hexagon 3)
2
Cable: remove the pins
3
Cable: Pull the cable out of the gravity weight
4
Shorten the cable/rod with a cut-off wheel or metal saw at the
lower end. Make sure the length is correct.
5
Cable: cable protrudes approx. 40 mm (1.575 in) into the gravity
weight.
6
Cable: Fasten the cable with three pins, torque 7 Nm (5.16 lbf ft)
7
Enter new probe length and then carry out a fresh adjustment (see
"Setup procedure, Carrying out min. adjustment - Carrying out
max. adjustment").