WORKING WITH SETPOINTS AND SETPOINT FILES
4–24
 Select the Actual > Product Info menu item and record the Software
Revision identifier of the relay firmware as shown below.
 Load the setpoint file to be upgraded into the EnerVista 745 Setup
environment as described in Adding Setpoints Files to the Environment
on page 4–22.
 In the File pane, select the saved setpoint file.
 From the main window menu bar, select the File > Properties menu
item and note the version code of the setpoint file.
If this version (e.g. 4.0X shown below) is different than the Software
Revision code noted in step 2, select a New File Version that matches
the software revision code from the pull-down menu.
For example, if the software revision is 2.80 and the current setpoint file
revision is 4.00, change the setpoint file revision to "4.0X", as shown
below.
 When complete, click Convert to convert the setpoint file to the desired
revision.
A dialog box will request confirmation. See Loading Setpoints from a
File on page 4–26 for instructions on loading this setpoint file into the
745.