GE 745 Instruction Manual page 144

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

S4 ELEMENTS
5.6.3
Differential Element
5.6.3.1 Main menu
DIFFERENTIAL [
5–48
EDIT SETPOINT GROUP: Select the number of the
are to be viewed and/or edited via the front panel keypad or any of the
communication ports. Selecting "Active Group" selects the currently active setpoint
group for editing.
GROUP 2(4) ACTIVATE SIGNAL: Select any logic input which, when asserted, will
(remotely) select
SETPOINT GROUP 2(4)
overridden if a higher number setpoint group is activated using the
setpoint or another logic input.
GROUP
PATH: SETPOINTS
S4 ELEMENTS

]
PERCENT
DIFFERENTIAL
HARMONIC
MESSAGE
INHIBIT
ENERGIZATION [
MESSAGE
INHIBIT
5th HARM
MESSAGE
INHIBIT
This section contains the settings to configure the percent differential element, including
all associated harmonic inhibit features. The 745 provides three independent harmonic
inhibit features:
HARMONIC INHIBIT
2nd + 5th harmonic which is 'in-circuit' at all times;
changing the characteristics of the inhibit scheme during energization to improve
reliability; and
5TH HARM INHIBIT
harmonic only, allowing inhibiting the percent differential during intentional overexcitation
of the system.
SETPOINT GROUP
to be the active group. This selection will be
DIFFERENTIAL

[
]
See page 5–49
[
]
See page 5–52
]
See page 5–53
[
]
See page 5–56
, which implements an inhibit scheme based on 2nd or
ENERGIZATION INHIBIT
, which implements an inhibit scheme based on 5th
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
whose settings
ACTIVE SETPOINT
, which allows