GE 745 Instruction Manual page 172

Transformer protection system
Hide thumbs Also See for 745:
Table of Contents

Advertisement

S4 ELEMENTS
5.6.9
Negative Sequence Overcurrent
5.6.9.1 Main Menu
NEG SEQ OC
5.6.9.2 Negative Sequence Time Overcurrent
W1 NEG SEQ
TIME OC
5–76
PATH: SETPOINTS
S4 ELEMENTS

[
]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
This section contains the settings to configure the negative sequence overcurrent
elements. Included are negative sequence time overcurrents for each winding, and
negative sequence instantaneous overcurrents for each winding.
PATH: SETPOINTS
S4 ELEMENTS

[
]
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
W1 (3) NEG SEQ TIME OC PICKUP: Enter the level of negative sequence current (in
units of relay nominal current) above which the winding 1(3) negative sequence time
overcurrent element will pickup and start timing.
W1 (3) NEG SEQ TIME OC SHAPE: Select the time overcurrent curve shape to be used
for the winding 1(3) negative sequence time overcurrent element. Refer to Time
Overcurrent Curves on page 5–59 for a description of the time overcurrent curve
shapes.
NEG SEQ OC

W1 NEG SEQ
[
]
TIME OC
W2 NEG SEQ
[
]
TIME OC
W3 NEG SEQ
[
]
TIME OC
W1 NEG SEQ
[
]
INST OC
W2 NEG SEQ
[
]
INST OC
W3 NEG SEQ
[
]
INST OC
NEG SEQ OC

W1 NEG SEQ TIME OC
FUNCTION: Enabled
W1 NEG SEQ TIME OC
RLYS (1-8): --------
W1 NEG SEQ TIME OC
TARGET: Latched
W1 NEG SEQ TIME OC
PICKUP: 0.25 x CT
W1 NEG SEQ TIME OC
SHAPE: Ext Inverse
W1 NEG SEQ TIME OC
MULTIPLIER: 1.00
W1 NEG SEQ TIME OC
RESET: Linear
W1 NEG SEQ TIME OC
BLOCK: Disabled
745 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
See page 5–76
See page 5–76
See page 5–76
See page 5–77
See page 5–77
See page 5–77
W1(3) NEG SEQ TIME OC
Range:
Enabled, Disabled
Range:
1 to 8
Range:
Self-Reset, Latched, None
Range:
0.05 to 20.00 x CT in steps of
0.01
Range:
see description below
Range:
0.00 to 100.00 in steps of 0.01
Range:
Instantaneous, Linear
Range:
Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled